EasyManua.ls Logo

FläktGroup HYPOWER-GEKO - Page 58

FläktGroup HYPOWER-GEKO
132 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical connection HyPower-Geko
58 FläktGroup DC-2014-0022-GB 2018-05/R5 • Subject to modifications
Connecting multiple HyPower-Geko units without FG-relay PCB
6.4.2 Connection of HyPower-Geko with EC motors
EC motors require 230 V AC 50 Hz supply voltage. 0-10 V DC or PWM signal is
required for for RPM regulation.
Multiple EC motors can be wired in parallel with regard to supply voltage and control
signal..
Pos. 1: Power supply 230 V AC / 50 Hz,
fusing by others max. B 6 A
Pos. 2: Speed selection switch
Pos. 3: HyPower-Geko Nr. 1, 3-speed fan
Pos. 4: HyPower-Geko Nr. 2, 3-speed fan
Connect multiple HyPower-Geko units in
accordance with the wiring diagram.
For 5-speed regulation an additional relay
is required. Use the given wiring diagram to
connect 3-speed fans.
Fig. 6-4: Connecting multiple HyPower-Geko units without FG-relay PCB
User instructions!
Multiple HyPower-Geko units without a FG-relay circuit board can be equipped and
combined with an external controller according to Fig. 6-4. Cut-off relays must be
provided by others (K1 - K3).
HyPower-Geko units with a FG-relay circuit board are prepared for parallel opera-
tion. Only one fan speed stage may be activated simultaneously!
A minimum switch pause of 0.1 sec. must be maintained between changing speeds!
According to the relevant regulations, an all-pole isolating device must be provided
by others on-site!
Speed 1 Speed 2Speed 3
Further slave units
Damage to the unit!
If multiple motors are installed in one unit, alarm signals must be tapped off for each
motor separately if a control system provided on-site is used. The error signal is
ground-referenced and a serial interconnection of multiple outputs can cause motor
damage. An overload of malfunction-report outputs can also cause motor damage.
Pos. 1: Alarm signals (not floating; max.
stress tolerance of 10 mA), terminals
11.1 = EC motor 1,
11.2 = EC motor 2 (only certain sizes,
refer to Tab. 6-5)
Pos. 2: Power supply 230 V AC; on-site fus-
ing max. 6 A
Pos. 3: Control signal 0-10 V DC 1 / PWM
(max. consumption of 0.1mA)
Pos. 4: Output voltage 10V DC
(max. loading capacity of 1mA)
Pos. 5: Connecting terminals for valves
Pos. 6: Connecting terminals for condensate
pump fault (optional)
Connect multiple HyPower-Geko units
in accordance with the wiring diagram.
Fig. 6-5: Connecting HyPower-Geko with EC motors

Table of Contents

Related product manuals