Loading...
7381
User’s Guide
30
Temperature Scale Units
Set the temperature scale units to degrees Celsius (°C) or Fahrenheit (°F). The Bath shows
these units for:
bath temperature
set-point
vernier
proportional band
cutout set-point
Access the temperature units after the vernier adjustment function.
1. Push SET.
2. From the Temperature Display function, push SET four times to access the units (
Un)
selection.
3. Push UP or DOWN to change the units (
C or F).
4. Push SET to store the new selection.
Program Menu
Use the Ramp and Soak Program feature to program a number of set-points and have the
Product automatically cycle between the temperatures, holding at each for a length of time.
Select one of four different cycle functions.
To show the program parameter (
ProG) menu:
1. Push SET and then UP.
2. Push SET to enter the program menu.
Number of Program Set-points
The first parameter in the Program menu is the number of set-points to cycle through. Set a
maximum of eight set-points for a ramp and soak program (
Pn=1 through Pn=8). These set-points
are independent from the programmable set-points described in Programmable Set-points.
To program a set-point:
1. Push the UP or DOWN buttons to change the number from 2 to 8.
2. Push SET to store the new value and continue, or push EXIT to ignore changes made and
continue.

Table of Contents