42
CHAPTER 7 – PARAMETER LISTS
CHAPTER 7 - PARAMETER LISTS
7.1 Primary Parameter Group
Code
Modbus
Address
FullParameterName
OLEDDisplay
Name
ParameterSettingRange
Adj.During
Run
1 101 Application Application 0‐Basic
1‐SupplyFan
2‐ExhaustFan
3‐CoolingTower
4‐Surface/BoosterPump
No
2 102 RatedMotorVoltage MotorVoltage 200/400Vmodel:200to
480V;default230V
400Vmodel:380to480V;
default460V
No
3 103 RatedMotorHP Motor
Horsepower
1to20HP No
4 104 RatedMotorCurrent MotorCurrent 0.5AtoVFDRating No
5 105 RatedMotorRPM MotorRPM 500to3600RPM No
6 106 PowerLineFrequency LineFrequency 0‐50[Hz]
1‐60[Hz]
No
7 107 MaximumFrequency MaxFrequency 30.00to240.00[Hz] No
8 108 BaseFrequency BaseFrequency 30.00toVFDMaxHz
[Primary‐07]
No
9 109 HighFrequencyLimit HighFrequency
Limit
VFDLowHzLimit
[Primary‐10]toVFDMax
Hz[Primary‐07]
No
10 110 LowFrequencyLimit LowFrequency
Limit
0.50toVFDHighHzLimit
[Primary10]
Yes
11 111 CarrierFrequency CarrierFrequency 2.0to10.0[kHz] No
15 115 Power‐OnRun Power‐OnRun 0‐Disable
1‐Enable
Yes
16 116 Power‐OnRunDelay Power‐OnRun
Delay
0to9999[Sec] Yes
