60
7.6 View Information Parameter Group
Code
Modbus
Address
FullParameterName
OLEDDisplay
Name
ParameterSettingRange
Adj.During
Run
1 601 VFDOutputFrequency OutputFrequency 0.00to240.00[Hz] N/A
2 602 MotorSpeed MotorSpeed 0to3600[RPM] N/A
3
603 Wattmeter[1] Wattmeter 0to4,294,967,295[kWh] N/A
604 Wattmeter[2]
5 605 AverageOutputCurrent AverageCurrent 0.0to6xVFDFLA[A] N/A
6 606 LineUCurrent LineUCurrent 0.0to6xVFDFLA[A] N/A
7 607 LineVCurrent LineVCurrent 0.0to6xVFDFLA[A] N/A
8 608 LineWCurrent LineWCurrent 0.0to6xVFDFLA[A] N/A
9 609 DCBusVoltage DCBusVoltage 0to1000[V] N/A
10 610 OutputVolta ge OutputVoltage 0to600[V] N/A
11 611 OutputStatus OutputStatus 0‐VFDOff
1‐Accelerate
2‐Decelerate
3‐Steady
4‐Speedsearch
5‐Flyingstart
6‐DCOutput
7‐Preheat
8‐DCtripprevention
9‐Stallprevention
10‐Bypassoff
11‐Bypassrun
N/A
12 612 SystemStatus SystemStatu s 0‐VFDstop
1‐VFDrun
2‐VFDdisabled
3‐VFDfault
4‐VFDshutdown
5‐VFDfireman's
override
6‐VFDautoreset
8‐Power‐ondelay
12‐Signalloss
14‐PIDrun
15‐Opendamper
18‐Bypassstop
19‐Bypassmanual
20‐Bypassoverride
22‐Bypassautoonfault
23‐Bypassdi
sabled
24‐Bypassfault
25‐Bypassshutdown
27‐Bypassautoon
commsloss
N/A