8.5 Protection
PROT-1: Preheat Mode
Preheat Mode
1) Disabled
0 - Disabled
1 - Low Heat
2 - Medium Heat
3 - High Heat
Default: Disabled
0‐PreHeatDisabled;
1‐Lowcurrentlevelwithlowdutycyclefor
cooltemperatures.VFDprovideslowlevelpre
heatcurrentwithlowdutycycle.Itshouldbe
enoughtokeepmotorwindingwarmduring
coolsummernights;
2‐Mediumcurrentlevelwithmediumduty
cycleforcoldtemperatures.VFDprovides
mediu
mlevelpreheatcurrentwithmedium
dutycycle.Itshould beenoughtokeepmotor
windingwarmduringcooldaysandcoldnights
inautumnorspring;
3‐HighcurrentlevelwithHighdutycyclefor
freezingtemperatures.VFDprovideshighlevel
preheatcurrentwithhighdutycy
cle.Itshould
beenoughtokeepmotorwindingwarmduring
colddaysandfreezingnightsinwinter.
PROT-3: No Motor Fault
No Motor Fault
3) Enabled
0 - Disable
1 – Enable
Default: Enabled
Allthreephaseshavecurrentbelow15%ofFLA
for250ms

PROT-4: Stall Prevention
Stall Prevention
4) Enabled
0 - Disable
1 – Enable
Default: Enabled
This works as a current limiting function
protecting motorfrom excessivecurrent above
the stall level setting by decreasing the motor
speed until the current is reduced to the stall
levelorspeedisreducedtotheminimumspeed.
PROT-5: Stall Level
Stall Level
5) 150%
Min: 30%
Max: 200%
Default: 150%
Stalllevelissetasapercentageofthemotor
FLA.
PROT-6: DC Trip Prevention
DC Trip Prevention
6) Enabled
0 - Disabled
1 – Enabled
Default: Enabled
EnablespreventionofDCTrip.
PROT-7: Overload Continuous
Ovld Continuous
7) 100%
Min: 50%
Max: 135%
Default: 100%
EOLcontinuouslevel(SFAifmotorcanrunatSF
24/7)EOLisalwaysenabledtoprotectmotor.
Overload Continuous is a percentage of
PRIMARY04 Motor FLA for continuous run
without EThermal trip. It can be set to motor
SFA(servicefactoramps)ifmotorisdesignedto
operateatse
rvicefactorampscontinuouslylike
submersible pump motors. For most of the
standardinduction motorsthis valueshouldbe
keptat100%(default).
PROT-8: Overload Trip Class
Ovld Trip Class
8) 10%
Min: 1%
Max: 50%
0 - Class 5
1 - Class 6 (Pump)
2 - Class 10
3 - Class 20
Default: 10%
Motoroverloadindustrystandardclasscurve
selections.(ONLYforVFD)
