57
Code
Modbus
Address
FullParameterName
OLEDDisplay
Name
ParameterSetting
Range
Adj.During
Run
39 439 CriticalFaultsRetryDelay CritFaultRetry
Delay
1to360[Min] Yes
40 440 LightFaultsNumberofAuto
Retries
LightFaultRetries 0to10 Yes
41 441 LightFaultsRetryDelay LightFaultRetry
Delay
1to360[Min] Yes
ProtectionGroupApplicationDefaults
Code
OLEDDisplay
Name
Basic SupplyFan ExhaustFan
Cooling
Tower
Surface/
Booster
Pump
1 PreheatMode (0)Disabled (0)Disabled (0)Disabled (0)Disabled (0)Disabled
3 NoMotorFault (1)Enable (1)Enable (1)Enable (1)Enable (1)Enable
4 StallPrevention (1)Enable (1)Enable (1)Enable (1)Enable (1)Enable
5 StallLevel 150% 150% 150% 150% 150%
6 DCTripPrevent (1)Enable (1)Enable (1)Enable (1)Enable (1)Enable
7 VFDMOL
Continuous
100[%] 100[%] 100[%] 100[%] 100[%]
8 VFDMOL (2)10 (2)10 (2)10 (2)10 (2)10
9 BypassMOL (2)10 (2)10 (2)10 (2)10 (2)10
12 Overcurrent
Level
200[%] 200[%] 200[%] 200[%] 200[%]
13 Overcurrent
Delay
0.1[sec] 0.1[sec] 0.1[sec] 0.1[sec] 0.1[sec]
38 CriticalFault
Retries
3 3 3 3 3
39 CriticalFault
RetryDelay
3 3 3 3 3
40 LightFault
Retries
3 3 3 3 3
41 LightFaultRetry
Delay
2 2 2 2 2