S90-600 O FRICK QUANTUM EVAPORATOR CONTROL PANEL
Page 12 OPERATION
“OPERATING STATUS” SCREEN -
SCREEN KEY SET
Following are the screen key selections for the “Operating
Status” screen:
· [Menu] – Shows the “Main Menu” screen for the
selected Zone.
· [Evaporator Mode] – The following control
modes can be selected:
· [Off] – All outputs are turned off and there is
no longer any temperature control or
defrosting.
· [Mode 1] – The zone will use the “Mode 1”
setpoints to control temperature until another
selection is made.
· [Mode 2] - The zone will use the “Mode 2”
setpoints to control temperature until another
selection is made.
· [Mode 3] - The zone will use the “Mode 3”
setpoints to control temperature until another
selection is made.
· [Auto] (Automatic) – The zone will change
what setpoints (Mode 1, Mode 2, or Mode 3)
to use for control based on the operator-
selected time of day in the zone’s “Time
Schedule”.
· [Defrost] - The zone will be controlled using
the Defrost setpoints.
· [Zone Overview] – Shows the “Zone Overview”
screen.
· [Login to Zone] - Shows a selection box for the
Zone ID. After a valid ID is entered, the
“Operating Status” screen for that zone is
displayed.
· [Previous Zone] - Shows the “Operating Status”
screen for the previous Zone ID.
· [Next Zone] - Shows the “Operating Status”
screen for the next Zone ID.