Name
S3 Turbo 18
1)
S3 Turbo 20
Test book number PB0310011 PB0900016
Nominal output kW 22.5 20
Boiler class as per EN 303-5: 2012 5
1.S3 Turbo 18 only available in Italy
Test data - Emissions in [mg/MJ]
1)
(nominal load)
Carbon monoxide (CO) mg/MJ 90 100
Nitrogen oxide (NOx) mg/MJ 91 93
Organic hydrocarbons (OGC) mg/MJ 6 7
Dust mg/MJ 7 7
Boiler efficiency % 91.1 90.8
1.The pollutant concentration is specified as a mass based on the energy content of the fuel fed to the combustion system in mg/MJ
Test data - Emissions in [mg/m³]
1)
(nominal load)
Carbon monoxide (CO) mg/m³ 133 147
Nitrogen oxide (NOx) mg/m³ 134 137
Organic hydrocarbons (OGC) mg/m³ 10 11
Dust mg/m³ 11 11
1.Emissions values based on dry flue gas at standard temperature and pressure (0°C, 1013 mbar) with a volume content of oxygen of 13%
Name S3 Turbo 30
S3 Turbo 30
1)
Test book number PB0910016 PB0910016_at
Nominal output kW 30 31
Boiler class as per EN 303-5: 2012 5 5
4 with partial load
inspection
1.S3 Turbo 30 with 31 kW nominal output only available in Austria and Italy
Test data - Emissions in [mg/MJ]
1)
(nominal load / partial load)
Carbon monoxide (CO) mg/MJ 62 / – 58 / 486
Nitrogen oxide (NOx) mg/MJ 84 / – 84 / 70
Organic hydrocarbons (OGC) mg/MJ 3 / – 3 / 20
Dust mg/MJ 7 / – 7 / 8
Boiler efficiency % 92.2 / – 93.3 / 92.4
1.The pollutant concentration is specified as a mass based on the energy content of the fuel fed to the combustion system in mg/MJ
Test data - Emissions in [mg/m³]
1)
(nominal load / partial load)
Carbon monoxide (CO) mg/m³ 91 / – 86 / 714
Nitrogen oxide (NOx) mg/m³ 124 / – 124 / 102
Organic hydrocarbons (OGC) mg/m³ 5 / – 4 / 30
Dust mg/m³ 10 / – 10 / 12
1.Emissions values based on dry flue gas at standard temperature and pressure (0°C, 1013 mbar) with a volume content of oxygen of 13%
Test report data
S3 Turbo 18 - 20
Test report data
S3 Turbo 30
Technology
3
Technical specifications