Name S3 Turbo 40 S3 Turbo 45
Test book number PB0920016 PB0340011
Nominal output kW 40 45
Boiler class as per EN 303-5: 2012 5
Test data - Emissions in [mg/MJ]
1)
(nominal load / partial load)
Carbon monoxide (CO) mg/MJ 47 / 296 55 / 190
Nitrogen oxide (NOx) mg/MJ 82 / 80 85 / 86
Organic hydrocarbons (OGC) mg/MJ 2 / 12 2 / 7
Dust mg/MJ 8 / 10 9 / 10
Boiler efficiency (nominal load / partial
load)
% 93.5 / 92.6 94.1
1.The pollutant concentration is specified as a mass based on the energy content of the fuel fed to the combustion system in mg/MJ
Test data - Emissions in [mg/m³]
1)
(nominal load / partial load)
Carbon monoxide (CO) mg/m³ 69 / 435 81 / 280
Nitrogen oxide (NOx) mg/m³ 120 / 118 125 / 127
Organic hydrocarbons (OGC) mg/m³ 2 / 18 3 / 11
Dust mg/m³ 11 / 14 14 / 15
1.Emissions values based on dry flue gas at standard temperature and pressure (0°C, 1013 mbar) with a volume content of oxygen of 13%
Test report data
S3 Turbo 40 - 45
3
Technology
Technical specifications