96
24 Cause: Battery too hot (external temperature sensor only)
Remedy:
- Check battery and if necessary, place in a suitable environment
- Check device settings
25 Cause: Battery too cold (external temperature sensor only)
Remedy:
- Check battery and if necessary, place in a suitable environment
- Check device settings
26 Cause: Cell fault detected
Remedy:
- Check battery
Status codes in the event of a charging error:
31 Cause: Time exceeded in I1 phase
Remedy:
- Check device setting for battery capacity (Ah)
- Check battery voltage, water level, etc.
32 Cause: Time exceeded in U1 phase
Remedy:
- Check device setting for battery capacity (Ah)
- Check battery voltage, water level, etc.
34 Cause: Ah exceeded
Remedy:
- Check device setting for battery capacity (Ah)
- Check battery voltage, water level, etc.
35 Cause: Time exceeded in I2 phase
Remedy:
- Check device setting for battery capacity (Ah)
- Check battery voltage, water level, etc.
36 Cause: Target voltage not reached in I2 phase (format characteristic only)
Remedy:
- Check battery voltage, water level, etc.
37 Cause: Time exceeded during Ri charging, power derating of device
Remedy:
- Check device setting for battery capacity (Ah)
- Check battery voltage, water level, etc.
38 Cause: The time in which the battery has to be completely charged is too short
Remedy:
- Check set time
Status codes in the event of a device fault / primary circuit:
500 Cause: Module 1 (top) temperature sensor faulty
Remedy:
- Replace primary power module
501 Cause: Module 2 (bottom) temperature sensor faulty
Remedy:
- Replace primary power module
502 Cause: PCB temperature sensor faulty
Remedy:
- Replace primary power module