EasyManua.ls Logo

Fronius Symo GEN24 6.0.Plus - Page 110

Fronius Symo GEN24 6.0.Plus
172 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
permissible again (see example below). This setting is only necessary if required by na-
tional standards and regulations. The value of the permissible power of feeding in per
phase must be set.
Example: "Limit per phase" (setting value: 2000 W)
Phase 1 Phase 2 Phase 3 Total
Max. possible production [W] 2000 2000 2000 6000
Set value
"Limit per phase" [W]
1000 3000
Load demand in the household
network [W]
2000 3000 5000 10000
Load coverage in the household
network via PV system [W]
1000 3000
Purchase from the public grid [W] 1000 2000 4000 7000
"Total DC system power"
Input field for the total DC system power in Wp.
This value is used if the "Maximum permitted feed-in power of the entire system" is spe-
cified in %.
"Maximum permitted feed-in power of the entire system"
Input field for the "Maximum permitted feed-in power of the entire system" in W or %
(setting range: -10 to 100%).
If there is no meter in the system or if a meter has failed, the inverter limits the power of
feeding in to the set value.
Example: Feed-in limitation
(without consideration of the efficiency)
PV system to Fronius inverter 5000 W
Loads in the house 1000 W
Maximum permitted feed-in power of the entire system 60% = 3000 W
Case 1: The battery can be charged
Power at grid feed-in point 0 W
Power at inverter output 1000 W
Power into the battery 3000 W
Case 2: The battery cannot be charged
Power at grid feed-in point 3000 W
Power at inverter output 4000 W
Power into the battery 0 W
In this example, no more than 3000 W may be fed into the public grid at the grid feed-
in point. However, any loads that are located between the inverter and the grid feed-in
point can be supplied by additional power from the inverter.
"Hard Limit"
If this value is exceeded, the inverter switches off within max. 5 seconds. This value must
be higher than the value set for "Soft Limit".
110

Table of Contents

Related product manuals