Combined solar module strings with total current
greater than 25 A.
PV generator settings:
PV 1: ON
PV 2: OFF
PV 1 + PV 2 (connected in parallel): ON
IMPORTANT!
The maximum current load of a single ter-
minal is 25 A. PV connection strings with a
total current of more than 25 A must be
split between both PV inputs upstream of
the terminals (≤ 56.25 A). The plug con-
nection for splitting the total current must
be sufficiently dimensioned, suitable and
correctly installed. Splitting the current by
bridging from PV 1 to PV 2 at the terminal
is not permitted.
PV 1 ≤ 37.5 A / PV 2 ≤ 18.75 A
PV generator settings:
PV 1: ON
PV 2: ON
Connecting the
solar module
strings to the in-
verter