Connection dia-
gram - 3 relays
The ripple control signal receiver and the I/Os terminal of the inverter can be connected
to one another in accordance with the connection diagram.
If the distance between the inverter and the ripple control signal receiver exceeds 10 m,
at least a CAT 5 cable is recommended and the shield must be connected at one end to
the push-in terminal of the data communication area (SHIELD).
(1) Ripple control signal receiver with 3 relays, for effective power limiting.
(2) I/Os of the data communication area.
Use the preconfigured file for 3-relay mode:
1
Download the file (.fpc) under 3-relay mode onto the end device.
2
Upload the file (.fpc) in the "I/O Power Management" menu using the "Import" button.
3
Click on the “Save” button.
The settings for 3-relay mode are stored.