Safety and grid requirements
Country setup The "Country setup" menu area is intended exclusively for installers/service technicians
from authorised specialist companies. The access code must be requested from the na-
tional/international Fronius point of contact using an application form.
The selected country setup for the respective country contains preset parameters ac-
cording to the nationally applicable standards and requirements. Depending on local grid
conditions and the specifications of the energy provider, adjustments to the selected
country setup may be necessary.
CAUTION!
Risk due to unauthorised access.
Incorrectly set parameters can negatively influence the public grid and/or the feed-in of
power into mains by the inverter, and lead to a loss of conformity with the standard.
The parameters may only be adjusted by installers/service technicians from author-
ised specialist companies.
Do not give the access code to third parties and/or unauthorised persons.
CAUTION!
Risk due to incorrectly set parameters.
Incorrectly set parameters can negatively influence the public grid and/or cause faults
and failures on the inverter, and lead to the loss of standard conformity.
The parameters may only be adjusted by installers/service technicians from author-
ised specialist companies.
The parameters may only be adjusted if the energy provider permits or requires this.
Only adjust the parameters taking into account the nationally applicable standards
and/or directives and the specifications of the energy provider.
Feed-in limitation Energy companies or grid operators may stipulate feed-in limitations for an inverter (e.g.
max. 70% of kWp or max. 5 kW).
The feed-in limitation takes account of self-consumption by the household before the
power of an inverter is reduced:
- A custom limit can be set.
- A Fronius Smart Meter can be connected to the Modbus push-in terminal of the data
communication area at the connections M0/M1- / M0/M1+ for Modbus data.
With the inverter, any PV power that is not allowed to be fed into the public grid is used
to charge the battery instead and/or used by the Fronius Ohmpilot so that it does not go
to waste. The feed-in limitation is only active if the power of feeding in is higher than the
set power reduction.
"Off"
The inverter converts the entire available PV power and feeds it into the public grid.
"Limit for entire system"
The entire PV system is limited in accordance with a set power limit. The value of the
permissible total feed-in power must be set.
"Limit per phase"
Each individual phase is measured. If the permissible feed-in limit is exceeded on one
phase, the total power of the inverter is reduced until the value on the affected phase is