IMPORTANT!
The inverter must not be installed or used at altitudes above 4000 m.
Do not install the inverter in:
- Areas where it may be exposed to ammonia, corrosive gases,
acids or salts (e.g. fertiliser storage areas, vent openings for live-
stock stables, chemical plants, tanneries, etc.)
During certain operating phases the inverter may produce a slight
noise. For this reason it should not be installed in an occupied living
area.
Do not install the inverter in:
- Areas where there is an increased risk of accidents from farm an-
imals (horses, cattle, sheep, pigs, etc.)
- Stables or adjoining areas
- Storage areas for hay, straw, chaff, animal feed, fertilizers, etc.
The inverter is essentially designed to be dustproof (IP 66). In areas of
high dust accumulation, dust deposits may collect on the cooling sur-
faces, and thus impair the thermal performance. Regular cleaning is
required in this case, see chapter Operation in dusty environments
on page 137. We therefore recommend not installing the inverter in
areas and environments with high dust accumulation.
Do not install the inverter in:
- Greenhouses
- Storage or processing areas for fruit, vegetables or viticulture
products
- Areas used in the preparation of grain, green fodder or animal
feeds
Choosing the loc-
ation of third-
party batteries
IMPORTANT!
Refer to the manufacturer's documents for the suitable location for third-party batteries.
Explanation of
symbols for the
installation posi-
tion
The inverter is suitable for vertical installation on a vertical wall or
column.