Max. output power 6000 W
Rated apparent power 6000 W
Nominal grid voltage 3 ~ NPE 220 V / 380 V
3 ~ NPE 230 V / 400 V
Min. grid voltage
154 V
1)
Max. grid voltage
280 V
1)
Max. output current
16.4 A
Nominal output current (at 230 V) 8.7 A
Current (inrush)
6)
9.9 A / 4 ms
Nominal frequency
50 / 60 Hz
1)
Nominal frequency for Full Backup
53 / 63 Hz
1)
Total harmonic distortion < 3.5%
Power factor cos phi
2)
0 - 1 (adjustable)
0.7 - 1 (recommended)
Max. permitted mains impedance Z
max
on
PCC
4)
None
Max. output fault current per period 80.7 A / 10 ms
AC output data PV Point
Max. output power 4133 W (for 5 s)
Rated power 3000 W
Nominal output current 13 A
Nominal grid voltage
1 ~ NPE 220 V / 230 V / 240 V
Nominal frequency
53 / 63 Hz
1)
Switchover time < 90 s
Power factor cos phi
2)
0 - 1
AC output data Full Backup
8)
Max. output power 12400 W (for 5 s)
Max. output power (per phase)
4133 W (for 5 s)
Rated power
6000 W
Rated power (per phase)
7)
3680 W
Nominal output current (per phase) 16 A
Nominal grid voltage 3 ~ NPE 220 V / 380 V
3 ~ NPE 230 V / 400 V
Nominal frequency for Full Backup
53 / 63 Hz
1)
Switchover time < 90 s
Power factor cos phi
2)
0 - 1
General data
Maximum efficiency 98.2%
European efficiency (U
mpp nom
)
97.7%
144