MPP voltage range
(at rated power)
278 - 800 V
Max. connected load (P
PV max
)
Total
PV 1
PV 2
15000 Wp
12500 Wp
7500 Wp
Max. processable PV power
Total
PV 1
PV 2
10300 Wp
10300 Wp
6000 Wp
Max. input voltage
at 1000 W/m² / -10 °C in an open circuit
1000 V
Feed-in start-up input voltage in grid oper-
ation
5)
80 V
Max. input current
PV 1
PV 2
25.0 A
12.5 A
Max. short circuit current of solar modules
(I
SC PV
)
PV 1
PV 2
37.5 A
18.75 A
Max. short circuit current
(I
SC PV1
+ I
SC PV2
= I
SC max
)
Total
56.25 A
Max. inverter backfeed current to the ar-
ray
3)
37.5 A
Number of inputs - PV 1 2
Number of inputs - PV 2 1
Max. capacity of the PV generator against
earth
2000 nF
DC input data battery
8)
Max. voltage 531 V / 700 V *
* only with suitable disconnection device
between inverter and battery in the event
of a fault
Min. voltage 160 V
Max. current 22 A
Max. output 10000 W
DC inputs 1
AC input/output data
Rated power (P
nom
) 10000 W
Max. output power 10000 W
Rated apparent power 10000 W
Nominal grid voltage 3 ~ NPE 220 V / 380 V
3 ~ NPE 230 V / 400 V