Loading...
Rated operational current and rated breaking capacity
Rated operational
voltage (U
e
)
Rated operational
current (I
e
)
I
(make)
/
I
(break)
rated operational
current (I
e
)
I
(make)
/
I
(break)
≤ 500 V
DC
14 A 56 A 36 A 144 A
600 V
DC
8 A 32 A 30 A 120 A
700 V
DC
3 A 12 A 26 A 88 A
800 V
DC
3 A 12 A 17 A 68 A
900 V
DC
2 A 8 A 12 A 48 A
1000 V
DC
2 A 8 A 6 A 24 A
Number of poles 1 1 2 2