6
Strip the insulation of the single conduct-
ors by 12 mm.
The cable cross section must be between
1.5 mm
2
and 10 mm
2
. Lift to open the ter-
minal's operating lever and insert the
stripped single conductor into the slot
provided, all the way up to the stop. Then
close the operating lever until it engages.
NOTE!
Only one conductor may be connected
to each pin. The conductors can be
connected without ferrules.
7
L1´ Phase conductor
Neutral conductor
PEN conductor
NOTE!
The PEN conductor must be produced
with ends that are permanently marked
blue, according to the national provi-
sions, and have a cross section of
10 mm².
8
Fasten the ground conductor and PEN
conductor to the ground electrode terminal
using a screwdriver (TX20) and a torque of
1.8-2 Nm.