2-20 2 Installation and Connection
FVR-C11S-EN
2
Fi
ure 2-3-13 Connection example of PLC terminal (when analo
si
nal is input from PLC)
1) Set SW7 at CM.
2) With this connection, the power is supplied from the PLC power suppl
to the external thermal O/L rela
.
So, OH2 trip is activated b
PLC power-off with the inverter turned on.
3) To prevent inverter trip with OH2 when the PLC power bein
turned off, do not select the THR terminal function and
use the inverter electronic thermal O/L rela
.
5) Connection to PLC (When analo
si
nal is input from PLC)
When SW7 is set at P24, pol
switch (F1) activates a current limit to
turn the power off.
12
V
U
W
13
11
30C
30B
30A
P1
P
+
N
-
P
+
M
FM
C1
+10VDC
250
22k
V
G
G
DC24V
STOP
RUN
PRG
RESET
FUNC
DATA
3
L1/L
L2/N
FWD
X1
X2
REV
P24/
CM
X3
0V
P24
CM
SW7
F1
4.7k
P24
(THR)
Frequenc
settin
POT (VR)
MCCB
External thermal rela
To X3
terminal
To
output
terminal
of PLC
Sin
le-phase
200V input
series
200 to 240V
50/60Hz
+24 to +27 VDC
To
round terminal
Pulse output
External
thermal
O/L rela
DC24V :
PLC power suppl
PLC
Analo
meter
Alarm output for
an
fault
Analo
monitor
To
round
terminal
To 11 terminal
CAUTION