9-2 9 Specifications
FVR-C11S-EN
9
9-2 Common Specifications
Item Specifications
Braking
Brakin
torque
5
[%]
150 100 50 30
DC injection
brakin
z
Startin
frequenc
: 3Hz (fixed), Brakin
current (0 to 100%),
Brakin
time ( 0.0 to 30.0s)
Protective structure
(IEC60529)
z
Closed t
pe IP20
Coolin
method
z
Self-coolin
z
Fan coolin
Mass [k
] 0.6 0.6 0.7 0.9 1.6 2.2
Notes:
1) A 4-pole standard motor is assumed as a nominal
applied motor.
2) Inverter output capacit
(kVA) at 220V.
3) When a momentar
power failure occurs, while rated
volta
e is applied 85% of load of nominal motor is
iven.
4) When an optional power-factor correctin
DC reactor is
used.
5) Avera
e brakin
torque where an unloaded motor
decelerates and stops from 60Hz operation. (Varies
accordin
to the motor efficienc
)
6) The specification is calculated on assumption that the
inverter is connected to a 500 kVA-equivalent power
transformer.
Item Specifications Remarks
Output frequency
Setting
Maximum
output frequenc
z
50 to 120Hz (in 1Hz steps)
Base
frequenc
z
50 to 120Hz (in 1Hz steps)
Startin
frequenc
z
1 to 6Hz (in 1Hz steps)
Carrier
frequenc
z
0.75 to 15kHz
(Vector-distribution PWM control selectable at
7kHz or less)
When operatin
at a carrier frequenc
of 9kHz or
above, the frequenc
ma
automaticall
drop to
8kHz to protect the inverter.