6 Protective Function 6-3
FVR-C11S-EN
6
Fi
ure. 6-2-1 How to input the reset command
6-2 Alarm Reset
To release the trip status, enter the reset command b
pressin
the re-
set ke
or from terminal (RST) after removin
the cause of the trip.
Since the reset command is an ed
e operation, be sure to input a com-
mand strin
such as OFF ON OFF as shown in Fi
ure 6-2-1.
When releasin
the trip status, set the operation command to OFF.
When the operation command is set to ON, check that operation starts
after resettin
.
If the cause of trippin
is Er1, reset the error and initialize data. If the
inverter is not reset, contact Fuji Electric.
If alarm reset is activated with operation si
nal ON, the inverter sud-
denl
restarts which ma
be hazardous. Be sure to disable the oper-
atin
si
nal when releasin
the trip status:
Otherwise fire could occur.
씯씯
Reset command
Ke
pad panel
displa
Alarm output
Normal displa
Alarm displa
Normal displa
OFF
OFF
ON
OFF
OFF
ON
10ms or more
Trip
WARNING