6 Protective Function 6-1
FVR-C11S-EN
6
6 Protective Function
6-1 List of protec-
tive functions
When the protective function is activated, inverter output is instantl
cut
off (while the motor coasts until it is stopped), and an alarm is issued,
and the details of the alarm are displa
ed on the ke
pad panel.
Alarm Name
Ke
pad
panel
displa
Contents of operation
Overcurrent
OC1
Durin
acceleration
If the inverter output current momentaril
ex-
ceeds the overcurrent detection level because of
an overcurrent in the motor or the short-circuit in
the output circuit, the output is shut down, an
alarm is issued, and the inverter is tripped.
OC2
Durin
deceleration
OC3
While runnin
at
constant speed
Overvolta
e
OU1
Durin
acceleration
If the DC volta
e of the main circuit exceeds the
overvolta
e detection level because of an in-
crease in the re
eneratin
current from the mo-
tor, etc., output is shut down, an alarm is issued,
and the inverter is tripped. However, protection
a
ainst inadvertent overvolta
e loadin
(e.
.
hi
h-volta
e line) mi
ht not be provided.
OU2
Durin
deceleration
OU3
While runnin
at
constant speed
Undervolta
eLU
If the DC volta
e of the main circuit falls below the undervolta
e de-
tection level because of a lowered power suppl
, output is shut down
to protect the inverter. If the restart function after momentar
power
failure is not activated, an alarm is issued and the inverter is tripped.
If the restart function is activated, the inverter restarts automaticall
with no alarm.
For further details of the protective function, refer to the descriptions
of Function F14.
Overheatin
of
heat sink
OH1
If the temperature of the heat sink used for coolin
the rectifier diodes
and IGBTs rises because of coolin
fan failure, etc., protective func-
tion is activated to stop operation, an alarm is issued, and the inverter
is tripped.