10-1 10 Options
FVR-C11S-EN
10
10 Options
Table 10-2-1 External Options
10-1 Built-in
Options
There is an optional built-in card for RS485 serial communication.
Ask at the inverter distributor for details.
10-2 External Options
Molded case circuit
breaker
The molded case circuit breaker (MCCB) is connected for protectin
the
main circuit wirin
to the inverter and for turnin
power on and off.
The rated current or the rated interruptin
capacit
varies accordin
to the
power suppl
specifications.
For input power-factor
correctin
AC reactor (ACR)
DC reactor (DCR)
This is connected in the followin
cases.
1. When the power transformer capacit
is more than 500 kVA
2. To reduce input harmonic current
The input power factor is improved to 0.75 to 0.85 (ACR).
The input power factor is improved to 0.9 to 0.95 (DCR).
3. If there is a th
ristor load in the same power suppl
, if the capacitor for
power-factor correctin
is turned on or off, or if the sur
e volta
e in the
power suppl
is lar
e (ACR onl
)
* The DC reactor is unnecessar
when the AC reactor is used.
Ma
netic contactor
(MC)
The inverter can be operated without connectin
the ma
netic contactor.
When the inverter protective function is activated, this should be connect-
ed to turn off the power for safet
.
Sur
e absorber This is connected to suppress the sur
e
enerated b
the excitin
coil
when switchin
on or off the ma
netic contactor and the control rela
.
S2-A-0 (for ma
netic contactor), S1-B-0 (for mini control rela
)
Frequenc
settin
POT
(VR)
This is connected when the frequenc
is set from the control circuit termi-
nal usin
inverter power.