FVR-C11S-EN
12-1 12 Compliance with standards
12
12 Compliance with standards
12-1 UL/cUL standards
[Applicable to products with
UL/cUL mark]
12-1-1 General
The UL standards stand for Underwriters Labo-
ratories Inc. and the
are safet
standards aim-
in
at prevention of fire and other accidents in
the United States, thereb
providin
protection
for operators, service personnel and other per-
sons.
The cUL standards are established b
UL in the
view of compliance with the CSA standards. The
effect of products certified for the cUL standards
is equal to that of products certified for the CSA
standards.
12-1-2 Precautions
When usin
the UL/cUL certified product, refer
to "Compliance with UL/cUL standards" on pa
e
2.
For connection, refer to Fi
. 12-1-1.
z
Open T
pe Equipment "indoor use onl
"
z
Suitable for use on a circuit capable or deliv-
erin
not more than 5,000 rms s
mmetrical
amperes, 240V maximum.
z
When Protected b
Class J Fuses.
z
Use 60/75 C CU wire onl
.
z
A Class 2 circuit wired with Class 1 wire.
z
Field wirin
connection must be made b
a
UL Listed and CSA Certified closed-loop ter-
minal connector sized for the wire
au
e in-
volved. Connector must be fixed usin
the
crimp tool specified b
the connector manu-
facturer.
z
Solid state motor overload protection is pro-
vided in each model.
Fi
. 12-1-1 Recommended wirin
G L1/L L2/N P1 P(+)
P(+) N(-) U V W G
M
3~
POWER INPUT FUSE
(See instruction
manual for ratin
.)
THRMAL
OL RY
[THR] [CM]