9 Specifications 9-1
FVR-C11S-EN
9
9 Specifications
9-1 Standard Specifications
Item Specifications
Inverter t
pe
FVR0.1C11S-7 FVR0.2C11S-7 FVR0.4C11S-7 FVR0.75C11S-7 FVR1.5C11S-7 FVR2.2C11S-7
Nominal applied
motor
1
[kW]
0.1 0.2 0.4 0.75 1.5 2.2
Output ratings
Rated output
capacit
2
[kVA]
0.26 0.53 0.95 1.5 2.6 3.8
Volta
e[V]
z
3-phase, 200V/50Hz, 200, 220, 230V/60Hz
(Proportional to input volta
e)
Rated current [A] 0.7 1.4 2.5 4.0 7.0 10.0
Overload
capacit
z
150% of rated current for 1 min.
Rated frequenc
z
50, 60Hz
Input power supply
Phases, Volta
e,
Frequenc
z
Sin
le-phase 200 to 240V 50/60Hz
Volta
e/
frequenc
variations
z
Volta
e: +10% to -10%, Frequenc
: +5% to -5%
Capabilit
for
volta
e dip
3
z
When the input volta
e drops 165V or more, the inverter can be operated
continuousl
. When the input volta
e drops below 165V from rated volt-
a
e, the inverter can be operated for 15ms.
Rated input
current
6
[A]
(with DCR)
1.2 2.0 3.5 6.5 11.8 17.7
(without DCR) 2.3 3.9 6.4 11.4 19.8 28.5
Required power
suppl
capacit
4
[kVA]
0.3 0.4 0.7 1.3 2.4 3.6