5-2 Details of Each Function
Data protection
Set data can be locked to prevent it from bein
g
chan
g
ed b
y
mistake when usin
g
the ke
y
pad
panel:
Data can be chan
g
ed.
Data is protected.
Data is chan
g
ed when the + or ke
y
are pressed simultaneousl
y
.
Frequenc
y
command
The followin
g
five values can be selected:
Ke
y
operation [ ke
y
]
Volta
g
e input
(terminal 12) (0 to + 10VDC)
Current input
(terminal C1) (4 to 20mADC)
Volta
g
e input (terminal 12)
+ current input (terminal C1)
Analo
g
settin
g
(POT built in inverter)
Operation method
The followin
g
four values can be selected: refer
to Table 2-3-3.
Ke
y
operation [ ke
y
]
The motor runs when the ke
y
is
pressed and decelerates to stop when
the ke
y
is pressed. The direction
of rotation depends on the FWD and
REV terminals as follows.
When the external power suppl
y
is
used (Set SW7 at CM.)
+24 to +27 VDC
supplied to FWD - P24/CM: Forward
+24 to +27 VDC
supplied to REV - P24/CM: Reverse
Operation is impossible when
+24 to +27 VDC is supplied to both or
none of FWD - P24/CM and
REV - P24/CM.
When the internal power suppl
y
is used
(Set SW7 at P24.)
FWD - P24/CM short-circuited: Forward
REV - P24/CM short-circuited: Reverse
Operation is impossible when both the
FWD and REV terminals or none of
them are short-circuited with the
P24/CM terminal.
Factor
y
settin
g
Chan
g
e durin
g
operation
0X
Factor
y
settin
g
Chan
g
e durin
g
operation
4X
F00
0
1
F01
0
1
2
3
4
CAUTION
Hi
g
h-speed operation can be set b
y
the inverter easil
y
. Carefull
y
check the
limit of the motor and machine before
chan
g
in
g
the settin
g
.
Otherwise in
j
uries could occur.
Factor
y
settin
g
Chan
g
e durin
g
operation
2X
F02
0