8 Maintenance and Inspection 8-2
FVR-C11S-EN
8
Check part Check item How to inspect Evaluation criteria
Environment
1. Check the ambient air tem-
perature, humidit
, vibra-
tion, atmosphere (dust,
as
oil mist, waterdrops)
2. Are forei
n matter or dan-
erous objects such as
tools not left around the
equipment?
1. Measure b
visu-
al inspection and
the meter.
2. With visual in-
spection
1. The specified stand-
ard value must be
satisfied.
2. No forei
n matter or
dan
erous objects
left near the inverter?
Volta
e
Are the volta
es in the main
circuit and the control circuit
normal?
Measure with the
multimeter.
The specified standard
value must be satisfied.
Ke
pad panel
1. Is the displa
hard to read?
2. Are the characters com-
plete?
1., 2. Visual
inspection
1., 2. The displa
can
be read and is not
abnormal.
Structure such
as a frame or
cover
1. Abnormal sound or vibra-
tion?
2. Loose bolts (part to be
ti
htened) ?
3. Deformation or dama
e?
4. Discoloration b
overheatin
?
5. Stains and dust?
1. With Visual in-
spection and
hearin
2. Ti
hten more
3., 4., 5.
With visual
inspection
1., 2., 3., 4., 5.
Not abnormal.
Main circuit
Comon
1. Loose and missin
bolts?
2. Deformation, cracks, dam-
a
e, and discoloration b
overheatin
and deteriora-
tion in the equipment and
the insulation?
3. Stains and dust?
1. Ti
hten more
2., 3. Visual
inspection
1., 2., 3.
Not abnormal.
Note: A discolored
short-circuitin
bar does not
indicate a
problem.