GE Multilin 239 Motor Protection Relay 7-17
7 COMMUNICATIONS 7 COMMUNICATIONS
7
022C Ground Current --- --- 0.1 x A F1 N/A
022D Current Unbalance --- --- % F1 N/A
022E Ground Current Scale Factor --- --- --- F114 N/A
022F 2
nd
Phase Current Scale Factor --- --- --- F1 N/A
0230 3
rd
Phase Current Scale Factor --- --- --- F1 N/A
0231 4
th
Phase Current Scale Factor --- --- --- F1 N/A
0232 Reserved
0233 Reserved
0234 Reserved
0235 Reserved
0236 Reserved
0237 Reserved
0238 MOTOR
CAPACITY
Motor Load --- --- % FLC F1 N/A
0239 Thermal Capacity --- --- % F1 N/A
023A Calculated Time To O/L Trip --- --- F39 F1 ---
023B Time To O/L Trip Units and Scale --- --- --- F39 ---
023C Time To Overload Reset --- --- 0.1xmin F1 ---
023D Reserved
023E Reserved
023F Reserved
0240 TEMPERATURE RTD 1 Temperature (RTD Option) --- --- °C F2**** N/A
0241 RTD 1 Temperature (RTD Option) --- --- °F F2**** N/A
0242 RTD 2 Temperature (RTD Option) --- --- °C F2**** N/A
0243 RTD 2 Temperature (RTD Option) --- --- °F F2**** N/A
0244 RTD 3 Temperature (RTD Option) --- --- °C F2**** N/A
0245 RTD 3 Temperature (RTD Option) --- --- °F F2**** N/A
0246 Thermistor --- --- --- F6 N/A
0247 RTD Sensor Failure Cause (RTD Option) --- --- --- F33 N/A
0248 Hottest Stator RTD Number (RTD Option) --- --- --- F1 N/A
0249 Hottest Bearing RTD Number (RTD Option) --- --- --- F1 N/A
024A Reserved
024B Reserved
024C Reserved
024D Reserved
024E Reserved
024F Reserved
Table 7–1: 239 MEMORY MAP (Sheet 5 of 18)
REG
ADDR
(HEX)
GROUP DESCRIPTION REGISTER
VALUE
RANGE
STEP
VALUE
UNITS &
SCALE
FOR-
MAT
FACTORY
DEFAULT VALUE
(CONVERTED)
1, 2, 3,
*
,
**
,
***
,
****
,
†,
See page 7–30 for explanation of Table notes.