7-22 239 Motor Protection Relay GE Multilin
7 COMMUNICATIONS 7 COMMUNICATIONS
7
1055 Reserved
1056 Reserved
1057 Reserved
1058 PHASE
S/C
Phase S/C Trip 0-3 1 --- F19 0 = OFF
1059 Phase S/C Pickup 10-110 1 0.1 xCT F1 100 = 10.0 xCT
105A Phase S/C Delay 0-60000 10 ms F1
‡
0 ms
105B Reserved
105C Reserved
105D Reserved
105E Reserved
105F Reserved
1060 IMMEDIATE
OVERLOAD
Immediate Overload Alarm 0-1 1 --- F20 0 = OFF
1061 Immediate Overload Pickup 5-110 1 0.1
xFLC F1 10 = 1.0 xFLC
1062 Inhibit On Start For 0-6001 1 s F1
3
6001 = UNLIMITED
1063 Reserved
1064 Reserved
1065 Reserved
1066 Reserved
1067 Reserved
1068 MECHANICAL
JAM
Mechanical Jam Function 0-4 1 --- F23 0 = OFF
1069 Mechanical Jam Pickup 1-100 1 0.1
xFLC F1 2.0 x FLC
106A Mechanical Jam Delay 0-250 1 s F1 2 s
106B Inhibit On Start For 0-6001 1 s F1
3
6001 = UNLIMITED
106C Reserved
106D Reserved
106E Reserved
106F Reserved
1070 UNDER-
CURRENT
Undercurrent Function 0-5 1 --- F21 0 = OFF
1071 Undercurrent Pickup 5-100 1
0.01xF
LC
F1 0.50 xFLC
1072 Undercurrent Delay 0-250 1 s F1 2 s
1073 Reserved
1074 Reserved
1075 Reserved
1076 Reserved
1077 Reserved
1078 UNBALANCE Phase Unbalance Trip 0-1 1 --- F20 1 = ON
Table 7–1: 239 MEMORY MAP (Sheet 10 of 18)
REG
ADDR
(HEX)
GROUP DESCRIPTION REGISTER
VALUE
RANGE
STEP
VALUE
UNITS &
SCALE
FOR-
MAT
FACTORY
DEFAULT VALUE
(CONVERTED)
1, 2, 3,
*
,
**
,
***
,
****
,
†, ‡
See page 7–30 for explanation of Table notes.