EasyManua.ls Logo

GE 750 - Description

GE 750
504 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10-
2
750/760 Feeder Management Relay GE Power Management
10.2 LOGIC INPUTS SETUP 10 S3 LOGIC INPUTS
10
10.2 LOGIC INPUTS SETUP 10.2.1 DESCRIPTION
Each logic input has two setpoints as shown below for Logic Input 1. The following points apply to all the logic
inputs:
The state of a contact input is either ‘Open’ or ‘Closed and is determined directly from the rear terminal
inputs.
The state of a virtual input is either ‘On’ orOffand can be set by the user either from serial communica-
tions or from the
ACTUAL VALUES \ A1 STATUS \ VIRTUAL INPUTS
menu.
The state of a logic input is eitherAsserted’ orNot-Asserted.
The state of logic input X (X = 1 to 14) is determined by combining the state of contact input X with the
state of virtual input X according to the
INPUT X ASSERTED LOGIC
setpoint; this is a limited form of program-
mable logic.
The state of logic input Y (Y = 15 to 20) is determined by the state of virtual input Y according to the
INPUT
Y ASSERTED LOGIC
setpoint; this is a limited form of programmable logic.
A logic function is invoked when its corresponding logic input is ASSERTED.
One logic input can invoke many logic functions if required.

Table of Contents

Other manuals for GE 750

Related product manuals