EasyManua.ls Logo

GE 750 - Fault Locator

GE 750
504 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
17-
44
750/760 Feeder Management Relay GE Power Management
17.8 MONITORING 17 COMMISSIONING
17
17.8.3 FAULT LOCATOR
Test Connections per Figure 17–1: RELAY TEST WIRING – WYE CONNECTION or Figure 17–2: RELAY
TEST WIRING – DELTA CONNECTION on page 17–4.
Because of the broad range of variables that can be encountered in actual systems a represen-
tative configuration with a set of impedances and instrument transformers have been chosen
to demonstrate these tests. The model used to calculate the voltage and current phasors for
the tests is a radial, 10 km long, three phase, four wire system of 13.8 kV nominal and 600 amp
feeder capacity. At the relay location there are wye-connected VTs rated 14400/120 V and CTs
rated 600/5 A. A prefault load of about 8.5 MVA exists on the feeder. The relay is a 5 Amp unit.
The source voltage (ahead of the source impedance) is 14.0 kV
1.6°. Any overcurrent feature, all of which can
cause a fault location calculation by tripping, set to a pickup current below the programmed test current, can be
used for the tests.
Procedure:
1. Program the test set with the following
prefault
voltages and currents.
V
an
= 67.8
;
V
bn
= 67.8
240°;
V
cn
= 67.8
120°;
I
a
= 2.9
330°;
I
b
= 2.9
210°;
I
c
= 2.9
90°
2. Program the test set with the following fault voltages and currents.
V
an
= 59.0
;
V
bn
= 67.4
241°;
V
cn
= 67.4
121°;
I
a
= 13.0
286°;
I
b
= 2.9
210°;
I
c
= 2.9
90°
This fault is from phase A to ground, placed 5.0 km from the relay.
3. Inject the prefault voltages and currents, then apply the fault. The relay should trip and determine the type
of fault (A-G), the distance to the fault (5.0 km) and the reactance to the fault (2.73
).
4. Program the test set with the following fault voltages and currents.
V
an
= 67.4
;
V
bn
= 60.3
242°;
V
cn
= 67.4
122°;
I
a
= 2.9
330°;
I
b
= 12.0
166°;
I
c
= 2.9
90°
This fault is phase B to ground, placed 6.0 km from the relay.
5. Inject the prefault voltages and currents, then apply the fault. The relay should trip and determine the type
of fault (B-G), the distance to the fault (6.0 km) and the reactance to the fault (3.27
).
6. Program the test set with the following fault voltages and currents.
V
an
= 67.4
;
V
bn
= 67.4
242°;
V
cn
= 61.3
120°;
I
a
= 2.9
330°;
I
b
= 2.9
210°;
I
c
= 9.9
47°
This fault is phase C to ground, placed 7.0 km from the relay.
7. Inject the prefault voltages and currents, then apply the fault. The relay should trip and determine the type
of fault (C-G), the distance to the fault (7.0 km) and the reactance to the fault (3.82
).
8. Program the test set with the following fault voltages and currents.
V
an
= 60.4
;
V
bn
= 67.4
242°;
V
cn
= 61.7
117°;
I
a
= 11.4
253°;
I
b
= 2.9
210°;
I
c
= 11.4
73°
This fault is phase A to C, placed 8.0 km from the relay.
9. Inject the prefault voltages and currents, then apply the fault parameters. The relay should trip and deter-
mine the type of fault (A-C), the distance to the fault (8.0 km) and the reactance to the fault (4.36
).
Model Impedances (
) Zpos = Zneg Zzero
Source 0.028 + j0.662 0.028 + j0.662
Feeder 1.250 + j5.450 5.280 + j15.79
NOTE

Table of Contents

Other manuals for GE 750

Related product manuals