10.7 BLOCK OVERCURRENT FUNCTIONS 10 S3 LOGIC INPUTS
10
BLOCK NEUTRL INST 2:
Disabled
Range: Disabled, Input 1, Input 2, ..., Input 20
Blocks the neutral instantaneous 2 overcurrent element.
BLK GROUND TIME:
Disabled
Range: Disabled, Input 1, Input 2, ..., Input 20
Blocks the ground time overcurrent element.
BLOCK GROUND INST:
Disabled
Range: Disabled, Input 1, Input 2, ..., Input 20
Blocks the ground instantaneous overcurrent element.
BLK SENSTV GND TIME:
Disabled
Range: Disabled, Input 1, Input 2, ..., Input 20
Blocks the sensitive ground time overcurrent element.
BLK SENSTV GND INST:
Disabled
Range: Disabled, Input 1, Input 2, ..., Input 20
Blocks the sensitive ground instantaneous overcurrent element.
BLOCK NEG SEQ TIME:
Disabled
Range: Disabled, Input 1, Input 2, ..., Input 20
Blocks the negative sequence time overcurrent element.
BLOCK NEG SEQ INST:
Disabled
Range: Disabled, Input 1, Input 2, ..., Input 20
Blocks the negative sequence instantaneous overcurrent element.