750/760 Feeder Management Relay
GE Power Management
14.7 TRANSFER 14 S7 CONTROL
14
Table 14–1: LOGIC INPUTS FOR INCOMER #1, #2, AND BUS TIE RELAYS
INPUT INCOMER #1 INCOMER #2 BUS TIE
1 Name:
Local Mode
Asserted Lo
ic:
Contact Open
Contact Close
Open | Von
Open | Voff
Closed | Von
Closed | Voff
Name:
Local Mode
Asserted Lo
ic:
Contact Open
Contact Close
Open | Von
Open | Voff
Closed | Von
Closed | Voff
Name:
Local Mode
Asserted Lo
ic:
Contact Open
Contact Close
Open | Von
Open | Voff
Closed | Von
Closed | Voff
2 Name:
Remote Close
Asserted Lo
ic:
Contact Open
Contact Close
Open | Von
Open | Voff
Closed | Von
Closed | Voff
Name:
Remote Close
Asserted Lo
ic:
Contact Open
Contact Close
Open | Von
Open | Voff
Closed | Von
Closed | Voff
Name:
Remote Close
Asserted Lo
ic:
Contact Open
Contact Close
Open | Von
Open | Voff
Closed | Von
Closed | Voff
3 Name:
Remote O
en
Asserted Lo
ic:
Contact Open
Contact Close
Open | Von
Open | Voff
Closed | Von
Closed | Voff
Name:
Remote O
en
Asserted Lo
ic:
Contact Open
Contact Close
Open | Von
Open | Voff
Closed | Von
Closed | Voff
Name:
Remote O
en
Asserted Lo
ic:
Contact Open
Contact Close
Open | Von
Open | Voff
Closed | Von
Closed | Voff
4 Name:
52a
or
52b Contact
Asserted Lo
ic:
Contact Close
Name:
52a
or
52b Contact
Asserted Lo
ic:
Contact Close
Name:
52a
or
52b Contact
Asserted Lo
ic:
Contact Close
5 Name:
Breaker Connected
Asserted Lo
ic:
Contact Close
Name:
Breaker Connected
Asserted Lo
ic:
Contact Close
Name:
Breaker Connected
Asserted Lo
ic:
Contact Close
6 Name:
Selected To Tri
Asserted Lo
ic:
Contact Open
Contact Close
Name:
Selected To Tri
Asserted Lo
ic:
Contact Open
Contact Close
Name:
Selected To Tri
Asserted Lo
ic:
Contact Open
Contact Close
7 Name:
Undervolta
e On Other
Source
Asserted Lo
ic:
Contact Close
Name:
Undervolta
e On Other
Source
Asserted Lo
ic:
Contact Close
Name:
Close From Incomer 1
Asserted Lo
ic:
Contact Close
8 Name:
Incomer 2 Breaker Closed
Asserted Lo
ic:
Contact Close
Name:
Incomer 1 Breaker
Closed
Asserted Lo
ic:
Contact Close
Name:
Incomer 1 Breaker Closed
Asserted Lo
ic:
Contact Close
9 Name:
Tie Breaker Connected
Asserted Lo
ic:
Contact Close
Name:
Tie Breaker Connected
Asserted Lo
ic:
Contact Close
Name:
Close From Incomer 2
Asserted Lo
ic:
Contact Close
10 Name:
Tie Breaker Closed
Asserted Lo
ic:
Contact Close
Name:
Tie Breaker Closed
Asserted Lo
ic:
Contact Close
Name:
Incomer 2 Breaker Closed
Asserted Lo
ic:
Contact Close
11
†
Name:
Block Transfer
Asserted Lo
ic:
Contact Open
Contact Close
Name:
Block Transfer
Asserted Lo
ic:
Contact Open
Contact Close
Name:
Block Transfer
Asserted Lo
ic:
Contact Open
Contact Close
12
†
Name:
Transformer Lockout
Asserted Lo
ic:
Contact Open
Contact Close
Name:
Transformer Lockout
Asserted Lo
ic:
Contact Open
Contact Close
13
†
Name:
Source Tri
Asserted Lo
ic:
Contact Open
Contact Close
Name:
Source Tri
Asserted Lo
ic:
Contact Open
Contact Close
†
Inputs 11, 12, and 13 are optional