GE Power Management 750/760 Feeder Management Relay 16-
87
16 COMMUNICATIONS 16.5 DNP 3.0 DEVICE PROFILE
16
The following table specifies the default variation for all objects returned by the relay. These are the variations
that will be returned for the object in a response when no specific variation is specified in a request.
DEFAULT VARIATIONS
Object Description Default Variation
1 Binary Input - Single Bit 1
2 Binary Input Change With Time 2
10 Binary Output Status 2
30 16-Bit Analog Input Without Flag 4
32 16-Bit Analog Input Change Without Time 2