4-24 Series 90™-30 PLC LONWORKS® Bus Interface Module User's Manual June 1997 GFK-1322A
4
Table 4-3. Configurable Network Image Parameters
Parameter When
Initialized
Basis for
Configuration
Changeable when
node is installed?
Compile-time option to prevent
field-override of initial setting?
Channel Bit rate compilation
or installation
node yes no
Domain ID installation domain yes no
Subnet/Node Address installation domain yes no
Group Address(es) installation node yes no
Neuron ID manufacture node no no
Acknowledged Service-
Explicit Messages
compilation network variable or
explicit message
no no
Acknowledged Service-
Network Variables
compilation
or installation
network variable or
explicit message
yes yes
Retry Count installation network variable or
explicit message
yes no
Authenticated Service-
Explicit Messages
compilation network variable or
explicit message
no no
Authenticated Service-
Network Variables
compilation
or installation
network variable or
explicit message
yes yes
Parameter when/where
initialized
basis for
configuration
changeable when node
is installed
compile-time option to prevent field-
override of initial setting
Authentication Key compilation
or installation
domain yes no
Number of Priority Slots installation node yes no
Priority Service-Explicit
Messages
compilation network variable or
explicit message
no no
Priority Service-Explicit
Network Variables
compilation
or installation
network variable or
explicit message
yes yes
Network Variable Types compilation network variable or
explicit message
no yes

Table of Contents