K-01 Language
Option: Function:
Defines the language to be used in the display.
The frequency converter is delivered with 4 different languages.
[0] * English Part of Language packages 1 - 4
P-07 Motor Power [kW]
Range: Function:
4.00 kW* [0.09 - 3000.00 kW] Enter the nominal motor power in kW according to the motor nameplate data. The default value corre-
sponds to the nominal rated output of the unit.
This parameter cannot be adjusted while the motor is running. Depending on the choices made in par.
K-03 Regional Settings, either par. P-07 Motor Power [kW] or par. P-02 Motor Power [HP] is made invisible.
P-02 Motor Power [HP]
Range: Function:
4.00 hp* [0.09 - 3000.00 hp] Enter the nominal motor power in HP according to the motor nameplate data. The default value corre-
sponds to the nominal rated output of the unit.
This parameter cannot be adjusted while the motor is running.
Depending on the choices made in par. K-03 Regional Settings, either par. P-07 Motor Power [kW] or par.
P-02 Motor Power [HP] Motor Power is made invisible.
F-05 Motor Rated Voltage
Range: Function:
400. V* [10. - 1000. V] Enter the nominal motor voltage according to the motor nameplate data. The default value corresponds
to the nominal rated output of the unit.
This parameter cannot be adjusted while the motor is running.
F-04 Base Frequency
Range: Function:
50. Hz* [20 - 1000 Hz] Select the motor frequency value from the motor nameplate data.
NB!
This parameter cannot be adjusted while the motor is running.
P-03 Motor Current
Range: Function:
7.20 A* [0.10 - 10000.00 A] Enter the nominal motor current value from the motor nameplate data. This data is used for calculating
motor torque, motor thermal protection etc.
NB!
This parameter cannot be adjusted while the motor is running.
P-06 Base Speed
Range: Function:
1420. RPM* [100 - 60000 RPM] Enter the nominal motor speed value from the motor nameplate data. This data is used for calculating
automatic motor compensations.
NB!
This parameter cannot be changed while the motor is running.