DR-25 Torque [Nm] High
Range: Function:
0.0 Nm* [-200000000.0 - 200000000.0 Nm] View the torque value with sign, applied to the motor shaft. Some motors supply more than 160% torque.
Consequently, the min. value and the max. value will depend on the max. motor current as well as the
motor used. This specific readout has been adapted to be able to show higher values than the standard
readout in par. DR-16 Torque [Nm].
3.17.3 DR-3# Drive Status
Parameters to view the drive status values.
DR-30 DC Link Voltage
Range: Function:
0 V* [0 - 10000 V] View a measured value. The value is filtered with an 30 ms time constant.
DR-32 Brake Energy /s
Range: Function:
0.000 kW* [0.000 - 10000.000 kW] View the brake power transmitted to an external brake resistor, stated as an instantaneous value.
DR-33 Brake Energy /2 min
Range: Function:
0.000 kW* [0.000 - 10000.000 kW] View the brake power transmitted to an external brake resistor. The mean power is calculated on an
average basis for the most recent 120 seconds.
DR-34 Heatsink Temp.
Range: Function:
0 °C* [0 - 255 °C] View the frequency converter heatsink temperature. The cut-out limit is 90 ± 5 °C, and the motor cuts
back in at 60 ± 5 °C.
DR-35 Drive Thermal
Range: Function:
0 %* [0 - 100 %] View the percentage load on the inverter.
DR-36 Drive Nominal Current
Range: Function:
10.00 A* [0.01 - 10000.00 A] View the inverter nominal current, which should match the nameplate data on the connected motor. The
data are used for calculation of torque, motor protection, etc.
DR-37 Drive Max. Current
Range: Function:
16.00 A* [0.01 - 10000.00 A] View the inverter maximum current, which should match the nameplate data on the connected motor.
The data are used for calculation of torque, motor protection, etc.
DR-38 Logic Controller State
Range: Function:
0* [0 - 100] View the state of the event under execution by the SL controller.
DR-39 Control Card Temp.
Range: Function:
0 °C* [0 - 100 °C] View the temperature on the control card, stated in °C.