Alarm Word Extended Status Word
Bit Hex Dec Alarm Word Alarm Word 2 Warning Word Warning
Word 2
Extended
Status Word
0 00000001 1 Brake Check ServiceTrip, Read/
Write
Brake Check Ramping
1 00000002 2 Pwr. Card Temp ServiceTrip, (re-
served)
Pwr. Card Temp Auto Tune Running
2 00000004 4 Earth Fault ServiceTrip, Type-
code/Sparepart
Earth Fault Start CW/CCW
3 00000008 8 Ctrl.Card Temp ServiceTrip, (re-
served)
Ctrl.Card Temp Slow Down
4 00000010 16 Ctrl. Word TO ServiceTrip, (re-
served)
Ctrl. Word TO Catch Up
5 00000020 32 Over Current Over Current Feedback High
6 00000040 64 Torque Limit Torque Limit Feedback Low
7 00000080 128 Motor Th Over Motor Th Over Output Current High
8 00000100 256 Motor Electronic OL
Over
Motor Electronic OL Over Output Current Low
9 00000200 512 Drive Overld. Drive Overld. Output Freq High
10 00000400 1024 DC under Volt DC under Volt Output Freq Low
11 00000800 2048 DC over Volt DC over Volt Brake Check OK
12 00001000 4096 Short Circuit DC Voltage Low Braking Max
13 00002000 8192 Inrush Fault DC Voltage High Braking
14 00004000 16384 Mains ph. Loss Mains ph. Loss Out of Speed Range
15 00008000 32768 Auto Tune Not OK No Motor OVC Active
16 00010000 65536 Live Zero Error Live Zero Error AC Brake
17 00020000 131072 Internal Fault KTY error 10V Low KTY Warn Password Timelock
18 00040000 262144 Brake Overload Fans error Brake Overload Fans Warn Password Protection
19 00080000 524288 U phase Loss ECB error Brake Resistor ECB Warn
20 00100000 1048576 V phase Loss Brake IGBT
21 00200000 2097152 W phase Loss Speed Limit
22 00400000 4194304 Network Fault Network Fault Unused
23 00800000 8388608 24 V Supply Low 24V Supply Low Unused
24 01000000 16777216 Mains Failure Mains Failure Unused
25 02000000 33554432 1.8V Supply Low Current Limit Unused
26 04000000 67108864 Brake Resistor Low Temp Unused
27 08000000 134217728 Brake IGBT Voltage Limit Unused
28 10000000 268435456 Option Change Encoder loss Unused
29 20000000 536870912 Drive Restored to
factory settings
Output freq. lim. Unused
30 40000000 1073741824 Safe Stop (A68) Safe Stop (A71) Safe Stop (W68) Safe Stop
(W71)
Unused
31 80000000 2147483648 Mech. brake low Dangerous Failure
(A72)
Extended Status Word Unused
Table 5.3: Description of Alarm Word, Warning Word and Extended Status Word
The alarm words, warning words and extended status words can be read out via serial bus or optional network for diagnose. See alsopar. DR-94 Ext. Status
Word.
WARNING 1, 10 Volts low:
The 10 V voltage from terminal 50 on the control card is below 10 V.
Remove some of the load from terminal 50, as the 10 V supply is overloaded.
Max. 15 mA or minimum 590 .
WARNING/ALARM 2, Live zero error:
The signal on terminal 53 or 54 is less than 50% of the value set in par.
AN-10 Terminal 53 Low Voltage, par. AN-12 Terminal 53 Low Current, par.
AN-20 Terminal 54 Low Voltage, or par. AN-22 Terminal 54 Low Current re-
spectively.
WARNING/ALARM 3, No motor:
No motor has been connected to the output of the frequency converter.
WARNING/ALARM 4, Mains phase loss:
A phase is missing on the supply side, or the mains voltage imbalance is too
high.
This message also appears in case of a fault in the input rectifier on the fre-
quency converter.
Check the supply voltage and supply currents to the frequency converter.
WARNING 5, DC link voltage high:
The intermediate circuit voltage (DC) is higher than the overvoltage limit of
the control system. The frequency converter is still active.
WARNING 6, DC link voltage low
The intermediate circuit voltage (DC) is below the undervoltage limit of the
control system. The frequency converter is still active.
WARNING/ALARM 7, DC over voltage:
If the intermediate circuit voltage exceeds the limit, the frequency converter
trips after a time.
Possible corrections:
Connect a brake resistor
Extend the ramp time
Activate functions in par. B-10 Brake Function
Increase par. SP-26 Trip Delay at Drive Fault