GENERAL
PRODUCTOPERATIONSCREEN MODECURVESREGISTERINSTALLATIONCONNECTION
LOCKS
EntelliGuard G
INTRO BREAKER ACCESSORIES TESTS APPENDIX
TRIP UNIT
OTHER
2-38
Time Current Curves (cold state), Protection Device
Curvas Tempo Intensidade (a Frio), Protecção LT
Curvas de disparo (en frío)
EntelliGuard GT Electronic Trip Unit
0,1
1
10
100
1000
10000
00,00100,0100,1
x Breaker Rating In
Tripping Time In Seconds (s)
- Time Current Curve
LT- Protection Device
- Band C-05
- Band C-10
- Band C-15
- Band C-21
7,2 x
ST protection - OFF
I protection set to 15 x Ie
(1)
2h
LT set at Breaker Rating In
Setting Range
Ie = 0,975, 0,9625, 0,95, 0,45 or 0,4 x In
Ir = 0,5 to 1 x Ie in steps of 0,25
Total Setting Range 0,2 - 1 x In
EntelliGuard GT Electronic Trip Unit
0,1
1
10
100
1000
10000
00,00100,0100,1
x Breaker Rating In
Tripping Time In Seconds (s)
- Time Current Curve
LT- Protection Device
- Band C-01
- Band C-18
7,2 x
ST protection - OFF
I protection set to 15 x Ie
(1)
2h
LT set at Breaker Rating In
Setting Range
Ie = 0,975, 0,9625, 0,95, 0,45 or 0,4 x In
Ir = 0,5 to 1 x Ie in steps of 0,25
Total Setting Range 0,2 - 1 x In
EntelliGuard GT Electronic Trip Unit
0,1
1
10
100
1000
10000
00,00100,0100,1
x Breaker Rating In
Tripping Time In Seconds (s)
- Time Current Curve
LT- Protection Device
- Band F-01
- Band F-05
- Band F-09
- Band F-13
- Band F-17
- Band F-21
2h
ST protection - OFF
I protection set to 15 x Ie
(1)
LT set at Breaker Rating In
Setting Range
Ie = 0,975, 0,9625, 0,95, 0,45 or 0,4 x In
Ir = 0,5 to 1 x Ie in steps of 0,25
Total Setting Range 0,2 - 1 x In
EntelliGuard GT Electronic Trip Unit
0,1
1
10
100
1000
10000
00,00100,0100,1
x Breaker Rating In
Tripping Time In Seconds (s)
- Time Current Curve
LT- Protection Device
- Band F-02
- Band F-06
- Band F-10
- Band F-14
- Band F-18
- Band F-22
2h
ST protection - OFF
I protection set to 15 x Ie
(1)
LT set at Breaker Rating In
Setting Range
Ie = 0,975, 0,9625, 0,95, 0,45 or 0,4 x In
Ir = 0,5 to 1 x Ie in steps of 0,25
Total Setting Range 0,2 - 1 x In