EntelliGuard G
TRIP UNIT
REGISTER
2.5
2.5.1 Communication register
Valid for Modbus and Profibus in A-Cyclic mode.
2-45
Communications Parameters Function 2
Reg.Variable Value Read/Write
5 Relay 1 Status 0- OFF, 1- ON Read
6 Relay 2 Status 0- OFF, 1- ON Read
9 Input 1 Status 0- OFF, 1- ON Read
10 Input 2 Status 0- OFF, 1- ON Read
27 Breaker position 0- OFF, 1- ON Read
34 Cassette Indication 0- OFF, 1- ON Read
35 Draw Out 0- OFF, 1- ON Read
44 Remote Close 0- OFF, 1- ON Read
------------------------------------------------------------------------------------------------------
Communications Parameters Function 3
Reg.Variable Value Read/Write
2 GF Protection Sum Enable 0-Disable, 1-Enable Read
5 No. of Poles 0-3 Pole, 1- 4 Pole Read
7 Full Metering Enable 0-Disable, 1-Enable Read
8 Neutral Position 0-Disable, 1-Enable Read
10 Long Time Protecti. Enable 0-Disable, 1-Enable Read
18 Agency Standard 0-UL, 1-IEC, 2-ANSI Read
19 Breaker type 8- EntelliGuard
20 GTU Model Type 4-GTU ACB Read
22 Current Sensor Rating 1-150A 8-1200A 15-5000A Read
2-200A 9-1600A 16-6000A
3-225A 10-2000A 17-630A
4-400A 11-2500A 18-1250A
5-600A 12-3000A 19-6400A
6-800 A 13-3200A 20-Universal spare
7-1000A 14-4000A
35 ZSI Enable 0-Disable, 1-GT-ST (Z), 2-GR-ST-Inst (T) Read
37 MCR Level Low 16 bits --- Read
38 MCR Level High 16 bits --- Read
39 HSISC Level Low 16 bits --- Read
40 HSICS Level High 16 bits --- Read
81 Instantaneous 0-Disable, 1-15X Switchable. Read
98 Breaker Serial Number - Low 16 bit - Read
99 Breaker Serial Number - High 16 bits - Read
107 Reduce Instantaneous 0- Disable, 1-Enable Read
202 EntelliGuard Ie setting 0- Undefined 23 - 1125, 46 - 3072, Read&Write
1- 250, 24 - 1196, 47 - 3104,
2 - 280, 25 - 1210, 48 - 3136,
3 - 315, 26 - 1225, 49 - 3200,
4 - 350, 27 - 1250, 50- 3840,
5 - 400, 28 - 1280, 51- 3880,
6 - 450, 29 - 1440, 52 - 3920,
7 - 500, 30- 1536,53 - 4000,
8 - 560, 31- 1552,54 - 4800,
9 - 605, 32 - 1568, 55 - 4850,
10- 610, 33 - 1600, 56 - 4900,
11- 615, 34 - 1800, 57 - 5000,
12 - 630, 35 - 1920, 58 - 6144,
13 - 720, 36 - 1940, 59 - 6208,
14 - 768, 37 - 1960, 60- 6272,
15 - 776, 38 - 2000, 61- 6400,
16 - 784, 39 - 2250, 62 - 160,
17 - 800, 40- 2400,63 - 180,
18 - 900, 41- 2425,64 - 380,
19 - 960, 42 - 2450, 65 - 385,
20- 970, 43 - 2500, 66 - 390,
21- 980, 44 - 2560,
22 -1000, 45 - 2880,
206 Neutral Pole Rating 0-50%, 1-63%, 2-100% Read/Write
207 ZSI Combination 0 Read/Write
1-GF 4-Instantaneous
2-GF&ST 5-GF and Inst
3-ST 7-GF, ST and Inst
208 PT Primary Voltage 120- 600 Read/Write
209 PT Connection 0- Ph-N 1- Ph-Ph Read/Write
210 Password Protection 0 to 20 16- Lock 19- Unlock Read/Write
211 Modbus Slave Address 8 bit value Read/Write
213 Comm. Setting 0- 300-8N2 7- 300-8O1 14- 300-8E1 Read/Write
1- 600-8N2 8- 600-8O1 15- 600-8E1
2- 1200-8N2 9- 1200-8O1 16- 1200-8E1
3- 2400-8N2 10- 2400-8O1 17- 2400-8E1
4- 4800-8N2 11- 4800-8O1 18- 4800-8E1
5- 9600-8N2 12- 9600-8O1 19- 9600-8E1
6- 19200-8N2 13- 19200-8O1 20- 19200-8E1
215 Long Time Trip Pickup 1- 0.5 5- 0.7 9- 090 Read/Write
2- 0.55 6-0.75 10- 0.95
3- 0.6 7-0.8 11- 1.0
4- 0.65 8-0.85
216 Long Time Trip Delay 0- Off 1- Band1 2- Band2...Max 22 Read/Write
217 Long Time Cooling Constant 0- goes to 0 1-12 min. cooling Read/Write
220 Frequency 0- 50Hz 1- 60Hz 2- 400Hz Read/Write
222 Short Time Trip Pickup 1- 1.5 9- 5.5 16- 9.0 Read/Write
2- 2.0 10- 6.0 17- 9.5
3- 2.5 11- 6.5 18- 10.0
4- 3.0 12- 7.0 19- 10.5
5- 3.5 13- 7.5 20- 11
6- 4.0 14- 8.0 21- 11.5
7- 4.5 15- 8.5 22- 12
8- 5.0
223 Short Time Trip Delay 0- Off 6- Band6 12- Band12 Read/Write
1- Band1 7- Band7 13- Band13
2- Band2 8- Band8 14- Band14
3- Band3 9- Band9 15 - Band 15
4- Band4 10- Band10 16 - Band 16
5- Band5 11- Band11 17 - Band 17
² ²
224 Short Time Kst 0- OFF 1- I t Low 2- I t Med. Read/Write
²
3- I t High
225 Instantaneous Trip Pickup 0 Off (For switchable Inst only) Read/Write
1- Invalid 11- 6.5 21- 11.5
2- 0 12- 7 22- 12
3- 2.5 13- 7.5 23- 12.5
4- 3 14- 8 24- 13
5- 3.5 15- 8.5 25- 13.5
6- 4 16- 9 26- 14
7- 4.5 17- 9.5 27- 14.5
8- 5 18- 10 28- 15
9- 5.5 19- 10.5
10- 6 20- 11
226 Reduced Instantaneous Trip Pickup 0- OFF (for switchable only) Read/Write
1- 1.5 11- 6.5 21- 11.5
2- 2 12- 7 22- 12
3- 2.5 13- 7.5 23- 12.5
4- 3 14- 8 24- 13
5- 3.5 15- 8.5 25- 13.5
6- 4 17- 9.5 27- 14.5
8- 5 18- 10 28- 15
9- 5.5 19- 10.5
10- 6 20- 11
233 GF Sum Trip Pickup 1- 0.10 82- 0.91
2- 0.11 83- 0.92
3- 0.12 In steps 84- 0.93
4- 0.13 of 0.01 85- 0.94
5- 0.14 Until 86- 0.95
6- 0.15 87- 0.96
7- 0.16 88- 0.97
8- 0.17 89- 0.98
9- 0.18 90- 0.99
10- 0.19 91- 1.00
234 GF Sum Delay Band 0- Off 6- Band6 12- Band12 Read/Write
1- Band1 7- Band7 13- Band13
2- Band2 8- Band8 14- Band14
3- Band3 9- Band9
4- Band4 10- Band10
5- Band5 11- Band11
²
235 GF Sum K Value 0- OFF 1- I t Low Read/Write
² ²
2- I t Medium 3- I t High' Read/Write
271 Relay1 (Output1) Function 1- Group 1 4- Group 4 7- Group 7 Read/Write
2- Group 2 5- Group 5
3- Group 3 6- Group 6
272 Relay2 (Output2) Function 1- Group 1 4- Group 4 7- Group 7 Read/Write
2- Group 2 5- Group 5
3- Group 3 6- Group 6
ENGLISH ENGLISH