D-12 F650 Digital Bay Controller GEK-113000AE
D.1 FACTORY DEFAULT SETTINGS APPENDIX D
D
SETPOINT > PRODUCT SETUP > DEMAND
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Function permission Demand Function DISABLED N/A [DISABLED – ENABLED]
Demand method for current values
CRNT Demand
Method
THERMAL
EXPONENTIAL
N/A
[BLOCK INTERVAL -
ROLLING DEMAND -
THERMAL EXPONENTIAL]
Demand method for Power values
POWER Demand
Method
THERMAL
EXPONENTIAL
N/A
[BLOCK INTERVAL -
ROLLING DEMAND -
THERMAL EXPONENTIAL]
Demand interval Demand Interval 5 Minutes N/A [5 – 10 – 15 – 20– 30–60]
Trigger Enabled Trigger Enabled DISABLED N/A [DISABLED – ENABLED]
Snapshot Event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]