2-34 F650 Digital Bay Controller GEK-113000AE
2.5 TECHNICAL SPECIFICATIONS 2 PRODUCT DESCRIPTION
2
2.5.12 ENVIRONMENTAL CHARACTERISTICS
2.5.13 PACKAGING AND WEIGHT
2.5.14 TYPE TESTS
Operating temperature:
- 10°C to + 60°C
Storage temperature:
- 40°C to + 85°C
Humidity (non condensing): 95%
Altitude Up to 2000 m
Class of equipment I
Equipment mobility Fixed
Overvoltage category III
Pollution degree 2
Net weight: 5 kg
Packaged: 6 kg
Package dimensions: 30x40x40 cm (DxWxH)
CATEGORY STANDARD CLASS TEST
SAFETY
Dielectric voltage withstand IEC60255-27 2 KV / 2.3 KV
Dielectric voltage withstand IEC60255-27 5 KV
Insulation resistance IEC60255-27 500 V (test level)
EMC
Electrostatic Discharge Immunity IEC60255-26/IEC61000-4-2 Level 4
Radiated RF Electromagnetic Field Immunity IEC60255-26/IEC61000-4-3 Level 3
Electrical Fast Transient Immunity IEC60255-26/IEC61000-4-4 Zone A
Surge Immunity IEC60255-26/IEC61000-4-5 Zone A
Conducted RF Immunity IEC60255-26/IEC61000-4-6 Level 3
Power magnetic Immunity IEC60255-26/IEC61000-4-8 Level 5
Power Frequency Immunity IEC60255-26/IEC61000-4-16 Zone A
Damped Oscillatory Wave Immunity IEC60255-26/IEC61000-4-18
2.5 KV Common Mode 1 KV Diff. Mode
Voltage Dips & Interruptions IEC60255-26/IEC61000-4-11/
IEC61000-4-29
Levels based on IEC61000-4-11 &
IEC61000-4-29
Ripple on DC IEC60255-26/IEC61000-4-17 15% Rated DC value
Radiated & Conducted Emissions IEC60255-26/CISPR11/
CISPR22
Class A
MECHANICAL
Sinusoidal Vibration IEC60255-21-1 Class 1
Shock & Bump IEC60255-21-2 Class 1
Seismic IEC60255-21-3 Class 2
Enclosure Protection IEC60255-27/IEC60529 IP52
CLIMATIC
Cold test (storage) IEC60068-2-1 -40˚C 16 hrs
Cold test (operational) IEC60068-2-1 -20˚C 16 hrs
Dry heat test (storage) IEC60068-2-2 85˚C 16 hrs
Dry heat test (operational) IEC60068-2-2 60˚C 16 hrs
Change of Temperature IEC60068-2-14 5 cycles (3+3) -20˚C/60˚C
Damp Heat Humidity Cyclic IEC60068-2-30 6 cycles (12+12) 55˚C @ 93% R.H.
Damp Heat steady state IEC60068-2-78 40˚C @ 93% R.H.