EasyManua.ls Logo

GE F650 - Page 298

GE F650
323 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GEK-113000AE F650 Digital Bay Controller D-17
APPENDIX D D.1 FACTORY DEFAULT SETTINGS
D
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Function permission Function DISABLED N/A [DISABLED – ENABLED]
Heating constant Heat Time Constant 6.0 0.1 min [3.0 : 600.0]
Cooling constant Cool Time Constant 2.00
0.01 times
Heat Time
Ct.
[1.00 : 6.00]
Pickup level Pickup Level 1.00 0.01 A [0.05 : 160.00]
Alarm level Alarm Level 80.0 0.10% [1.0 : 110.0]
Snapshot event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]

Table of Contents

Other manuals for GE F650

Related product manuals