EasyManua.ls Logo

GE F650 - Page 305

GE F650
323 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
D-24 F650 Digital Bay Controller GEK-113000AE
D.1 FACTORY DEFAULT SETTINGS APPENDIX D
D
SETPOINT > CONTROL ELEMENTS > OVERFREQUENCY
OVERFREQUENCY 1 > OVERFREQUENCY 2 > OVERFREQUENCY 3
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Function permission Function DISABLED N/A [DISABLED – ENABLED]
Pickup level Pickup Level 50.50 0.01 Hz [20.00 : 65.00]
Trip time Trip Delay 0.00 0.01 s [0.00 : 900.00]
Reset time Reset Delay 0.00 0.01 s [0.00 : 900.00]
Minimum voltage threshold Minimum Voltage 30 1 V [10 : 300]
Snapshot event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]
SETPOINT > CONTROL ELEMENTS > SYNCHROCHECK
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Function permission Function DISABLED N/A [DISABLED – ENABLED]
Dead bus voltage level Dead Bus Level 10.00 0.01 V [0.00 : 300.00]
Live bus voltage level Live Bus Level 50.00 0.01 V [0.00 : 300.00]
Dead line voltage level Dead Line Level 10.00 0.01 V [0.00 : 300.00]
Live line voltage level Live Line Level 50.00 0.01 V [0.00 : 300.00]
Voltage Difference Max Volt Difference 10.00 0.01 V [2.00 : 300.00]
Angle Difference Max Angle Difference 10.0 0.1 Deg [2.0 : 80.0]
Frequency Slip Max Freq Difference 20 10 mHz [10 : 5000]
Breaker Closing time Time 0.50 0.01 s [0.01 : 600.00]
Dead Line – Dead Bus Function
permission
DL-DB Function DISABLED N/A [DISABLED – ENABLED]
Live Line – Dead Bus Function
permission
LL-DB Function DISABLED N/A [DISABLED – ENABLED]
Dead Line – Live Bus Function
permission
DL-LB Function DISABLED N/A [DISABLED – ENABLED]
Snapshot event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]
SETPOINT > CONTROL ELEMENTS > AUTORECLOSE
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Function permission Function DISABLED N/A [DISABLED – ENABLED]
Maximum Number of shots Max Number Shots 1 N/A [1 : 4]
Dead time 1 Dead Time 1 0.00 0.01 s [0.00 : 900.00]
Dead time 2 Dead Time 2 0.00 0.01 s [0.00 : 900.00]
Dead time 3 Dead Time 3 0.00 0.01 s [0.00 : 900.00]
Dead time 4 Dead Time 4 0.00 0.01 s [0.00 : 900.00]
Reclaim time or reset lockout delay Reclaim Time 0.00 0.01 s [0.00 : 900.00]
Reclose conditions permission Cond. Permission DISABLED N/A [DISABLED – ENABLED]
Hold time Hold Time 0.00 0.01 s [0.00 : 900.00]
Reset time Reset Time 0.00 0.01 s [0.00 : 900.00]
Snapshot event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]

Table of Contents

Other manuals for GE F650

Related product manuals