CHAPTER 2: PRODUCT DESCRIPTION SECURITY
M60 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL 2-5
2
Figure 2-2: CyberSentry user roles
The table lists user roles and their corresponding capabilities.
Table 2-3: Permissions by user role for CyberSentry
Roles Administrator Engineer Operator Supervisor Observer
Complete access Complete access
except for
CyberSentry
Security
Command
menu
Authorizes
writing
Default role
Device Definition R R R R R
Settings
|---------- Product Setup
|--------------- Security
(CyberSentry)
RW R R R R
|--------------- Supervisory See table notes R R See table
notes
R
|--------------- Display Properties RW RW R R R
|--------------- Clear Relay Records
(settings)
RW RW R R R
|--------------- Communications RW RW R R R
|--------------- Modbus User Map RW RW R R R
|--------------- Real Time Clock RW RW R R R
|--------------- Oscillography RW RW R R R
|--------------- Data Logger RW RW R R R
|--------------- Demand RW RW R R R
|--------------- User-Programmable
LEDs
RW RW R R R
|--------------- User-Programmable
Self Tests
RW RW R R R
|--------------- Control Pushbuttons RW RW R R R
|--------------- User-Programmable
Pushbuttons
RW RW R R R
|--------------- Flex state
Parameters
RW RW R R R
|--------------- User-Definable
Displays
RW RW R R R
|--------------- Direct I/O RW RW R R R
|--------------- Teleprotection RW RW R R R
|--------------- Installation RW RW R R R
|---------- System Setup RW RW R R R