1–12 MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
SPECIFICATIONS CHAPTER 1: INTRODUCTION
Testing and certification
TESTING AND CERTIFICATION
Test Reference Standard Test Level
Dielectric Voltage Withstand: EN60255-5 2.3KV (1 minute)
Impulse Voltage Withstand: EN60255-5 5KV
Damped Oscillatory: IEC61000-4-18IEC60255-22-1 2.5KV CM, 1KV DM
Electrostatic Discharge: EN61000-4-2/IEC60255-22-2 Level 4
RF Immunity: EN61000-4-3/IEC60255-22-3 Level 3
Fast Transient Disturbance: EN61000-4-4/IEC60255-22-4 Class A
Surge Immunity: EN61000-4-5/IEC60255-22-5 Level 3
Conducted RF Immunity: EN61000-4-6/IEC60255-22-6 Level 3
Voltage Interruption and Ripple DC: IEC60255-11 15% ripple , 200ms
interupts
Radiated & Conducted Emissions: CISPR11 /CISPR22/ IEC60255-25 Class A
Sinusoidal Vibration: IEC60255-21-1 Class 1
Shock & Bump: IEC60255-21-2 Class 1
Power magnetic Immunity: IEC61000-4-8 Level 5
Pulse Magnetic Immunity: IEC61000-4-9 Level 4
Voltage Dip & Interruption: IEC61000-4-11 0,40,70% dips,250/300cycle
interrupts
Damped Oscillatory: IEC61000-4-12 2.5KV CM, 1KV DM
Harmonics & Interharmonics: IEC61000-4-13 Class 3
Voltage Ripple: IEC61000-4-17 15% ripple
Ingress Protection: IEC60529 IP20 (base unit) , IP54
(Control Panel)
Environmental (Cold): IEC60068-2-1 -25
o
C 16 hrs
Environmental (Dry heat): IEC60068-2-2 70
o
C 16hrs
Relative Humidity Cyclic: IEC60068-2-30 6-day variant 2
APPROVALS
Applicable Council Directive According to
CE compliance: Low voltage directive EN60255-5, EN61010-1
EMC Directive EN50263 / EN61000-6-2/ EN61000-6-4
North America: cULus UL1053 [e83849 NKCR]
UL508 [e83849 NKCR]
C22.2-14 [e83849 NKCR7]
EAC Machines and Equipment TR CU 010/2011
ISO: Manufactured under a registered
quality program
ISO9001