Chapter 5. Diagnostics
124 PACSystems* RX3i & RSTi-EP PROFINET IO-Controller User Manual GFK-2571N
Group/
Category/
Type/
Descriptor
Description
Cause
Recommended
Correction
28-46-0-0
Diagnosis Appears
PROFINET Alarm
received (Alarm
contains only
Maintenance
status).
A PROFINET Alarm has
been received indicating
that a diagnostic condition
has been detected on the
PROFINET device.
Consult Device manufacturer
documentation.
Note: Alarm details are provided in
the Fault Extra Data.
28-47-0-0
Diagnosis
Disappears
PROFINET Alarm
received (Alarm
contains only
Maintenance
status).
A PROFINET Alarm has
been received indicating
that a diagnostic condition
has been resolved on the
PROFINET device and
maintenance is no longer
required.
None.
Note: Alarm details are provided in
the Fault Extra Data.
28-48-0-0
Diagnosis Appears
PROFINET Alarm
received.
A PROFINET Alarm has
been received indicating
that a diagnostic condition
has been detected on the
PROFINET device.
Consult Device manufacturer
documentation.
Note: Alarm details are provided in
the Fault Extra Data.
28-49-0-0
Diagnosis
Disappears
PROFINET Alarm
received.
A PROFINET Alarm has
been received indicating
that a diagnostic condition
has been resolved on the
PROFINET device.
None.
Note: Alarm details are provided in
the Fault Extra Data
28-50-0-0
PROFINET Status
Alarm received.
A PROFINET Alarm has
been received indicating a
status change on the
PROFINET Device.
Consult Device manufacturer
documentation.
Note: Alarm details are provided in
the Fault Extra Data
28-51-0-0
PROFINET Update
Alarm received.
A PROFINET Alarm has
been received indicating a
change to an operating
parameter has been made
by an external device.
Consult Device manufacturer
documentation.
Note: Alarm details are provided in
the Fault Extra Data
28-52-0-0
Port Data Change
PROFINET Alarm
received (Alarm
contains
manufacturer
specific data).
A PROFINET Alarm has
been received indicating a
Port change on the
PROFINET device.
Consult Device manufacturer
documentation.
Note: Alarm details are provided in
the Fault Extra Data
28-53-x
14
-0
Port Data Error
Appears PROFINET
Alarm received.
A PROFINET Alarm has
been received indicating
that a Port Error has
occurred on the PROFINET
device.
Consult Device manufacturer
documentation.
Note: Alarm details are provided in
the Fault Extra Data
28-54-x
14
-0
Port Data Error
Disappears
PROFINET Alarm
received.
A PROFINET Alarm has
been received indicating
that a Port Error condition
has been resolved on the
PROFINET device.
None.
Note: Alarm details are provided in
the Fault Extra Data