Appendix A. PROFINET IO Performance Examples
154 PACSystems* RX3i & RSTi-EP PROFINET IO-Controller User Manual GFK-2571N
A-2.2 VersaMax System Descriptions
A. 1ms PROFINET Update Rate Systems
A.1 Single Device
This system contained an IC695CPU315, IC695ETM001, and an IC695PNC001 in the main RX3i rack. The
PNC001 was connected to a single VersaMax PNS (IC200PNS001) configured for a 1 ms PROFINET update rate.
The PNS contained four mixed discrete 16 point in/out modules (IC200MDD844). Each I/O module had its
outputs tied to the inputs of an adjoining I/O module, and each input module was configured with a 1 ms Input
DC Filter time. The I/O Loopback measurement was taken using one of the IC200MDD844 modules.
A.2 Multi-Device
This system contained an IC695CPU315, IC695ETM001, and an IC695PNC001 in the main RX3i rack. The
PNC001 was connected in a network bus configuration to eight different VersaMax PNS modules
(IC200PNS001), each configured for a 1ms PROFINET update rate. Each PNS contained at least one discrete
input or output module. The I/O Loopback measurement was taken using a 16-point output module
(IC200MDL741) owned by one VersaMax PNS, that was then tied to the 16-point input module (IC200MDL640)
owned by a different VersaMax PNS. The input module (IC200MDL640) was configured for a 0 ms Input DC
Filter time.
A.2.1 - Multi-Device with MRP
This system is identical to the A.2 Multi-Device configuration, except that Media Redundancy Protocol (MRP)
was in use. To exercise MRP, the network was set up in a ring configuration and the PNC001 was configured as
an MRP Manager with a configured Default Test Interval of 20ms.
A.3 - Multi-PNC001 Multi-Device
This system contained an IC695CPU315, two IC695ETM001’s, an IC694MDL732, an IC694MDL645, and four
IC695PNC001 modules in the main rack. Each PNC001 module was connected in a network bus configuration
to eight VersaMax PNS modules (IC200PNC001), each configured for a 1ms PROFINET update rate. Each PNS
contained at least one discrete input, discrete output, analog input, or analog output module. The I/O Loopback
measurement was taken using a 16-point output module (IC200MDL741) owned by one VersaMax PNS, that
was then tied to the 16-point input module (IC200MDL640) owned by a different VersaMax PNS. The input
module (IC200MDL640) was configured for a 1 ms Input DC Filter time.