Chapter 6 Redundant Media
The PACSystems PROFINET Controller supports PROFINET Media Redundancy Protocol (MRP). The PROFINET
Controller can be used as either a Media Redundancy Manager or Media Redundancy Client on a redundant
media ring.
Media Redundancy enables the network to recover from a failure at any single network link or network node.
Because it operates transparently to applications using the network, no changes to the application are needed
to use media redundancy.
This chapter describes:
PROFINET Media Redundancy Protocol
MRP Performance
Ring Topology with One Controller
Ring Topology with Multiple Controllers
Setting Up Media Redundancy Protocol for a PROFINET IO-Controller
Sequence for Enabling Media Redundancy
Sequence for Replacing a Media Redundancy Manager
Procedure for Disabling Media Redundancy
The following table shows which PROFINET Scanners/Devices support MRP.
PROFINET Scanner/Device
Acronym
PROFINET Media Redundancy
Protocol (MRP)
RX3i CEP Carrier
RX3i CEP
RX3i Genius* Communications Gateway
RX3i GCG
PAC8000 PROFINET Scanner (PNS) Module
PAC8000 PNS
RSTi PROFINET Network Adaptor
RSTi PNS
RSTi-EP PROFINET Network Adaptor
RSTi-EP PNS
RX3i PROFINET Scanner (PNS) Module
RX3i PNS
VersaMax PROFINET Scanner (PNS) Module
Versamax PNS
VersaMax IP PROFINET Scanner Module
VersaMax/IP PNS
16
VersaPoint PROFINET Scanner
VersaPoint PNS
16
Bumpless operation is only guaranteed at IO Update rates at or above 128 ms